KCC110 AC Current Imbalance Protection, Analog Output

Call for price

AC Current Imbalance Protection
Download:
KCC110x Brochure

Description

KCC110x

AC CURRENT IMBALANCE PROTECTION

  • 2-level AC Current Imbalance Protection
  • True RMS measurement not affected by heavily distorted wave forms
  • 3 or 4-wire systems. Definite time trip delays
  • Total processing time less than 60mS
  • For use with 1A or 5A current transformers
  • DIN96 Slave Indicator (Scaled 0-40%In) with status LED’s (Optional)
  • Up to two individual very fast analog output signals (<50mS)< (Optional)
Description
KCC110E, KCC110G, KCC110Fx or KCC110GFx digitally controlled monitor and convert the three current transformer (CT) inputs into a signal proportional to the difference between the HIGHEST and the LOWEST input level.
The difference (imbalance) is displayed as a percentage of the CT rating. The standard scale range is 0 to 40%CT. The warning and alarm trip relays are settable over the same range.
Relay R1 is used for early warning. R2 (fail safe) can be used for generator breaker trip. R3 can be used for local indication, input to PMS, alarm system etc. Alarm trip must be sufficiently high to ensure that generator magnetization current does not cause tripping.
The alarm delay is to be set so that the initial inrush current have returned to normal level before the delay period elapses. The warning trip level and delay can be set as required to give early warning.
Fast response analogue output signal proportional to a range (KCC110Fx & KCC110GFx).
User settable trip levels and delays. Color of LED’s indicate alarm status. LED’s flash during count-down.
The “Pathfinder” (only on latching models) indicates the phase causing the trip by flashing pattern of the relevant LED.

Additional information

Weight 2 lbs
Dimensions 9 × 9 × 9 in
Model

KCC110E AC Current Imbalance Protection, without Analog Output, KCC110FA AC Current Imbalance Protection, with One Analog Output, KCC110FB AC Current Imbalance Protection, with Two Analog Output, KCC110G AC Current Imbalance Protection, without Analog Output, Latching Output, KCC110GFA AC Current Imbalance Protection, with One Analog Output, Latching Output, KCC110GFB AC Current Imbalance Protection, with Two Analog Output, Latching Output

Aux Supply

100-120VAC Aux Supply, 200-240VAC Aux Supply, 380-415VAC Aux Supply, 440-460VAC Aux Supply, 480VAC Aux Supply, 24-60VDC Aux Supply, 110-220VDC Aux Supply

Analog Output One

No Analog Output, 0-10mA Analog Output, 0-20mA Analog Output, 4-20mA Analog Output, 0-10VDC Analog Output, 0.2-10VDC Analog Output, 4.3-20mA Analog Output

Analog Output Two

No Analog Output, 0-10mA Analog Output, 0-20mA Analog Output, 4-20mA Analog Output, 0-10VDC Analog Output, 0.2-10VDC Analog Output, 4.3-20mA Analog Output

Current Input

1A, 5A