KPM163 Insulation Monitor, System Voltage up to 6.6kVAC, Output Relays, Optional Analog Output

$ 938.00$ 1,177.00

INSULATION MONITOR FOR NON-GROUNDED AC NETWORKS
Download:
KPM163x Brochure
Drawings:
KPM Dimensions

Description

KPM163

Insulation Monitor, System Voltage up to 6.6kVAC, Output Relays and Optional Analog Output

  • Direct connection up to 690V direct line voltage, up to 6,6kV with HV adapter
  • Monitoring during both live and standby conditions
  • For use in land, marine, offshore, sub-sea and ocean floor Installations
  • Triple-zone insulation monitoring
  • Comply with AODC 035 Code of Practice
  • “Megger” – safe to 1,4kVDC when aux power is OFF
  • Immune to earth capacitance and voltage surges
  • Analogue output proportional to meter reading (F-version)
Application
The digitally controlled KPM163x series monitors insulation level between a non-grounded (IT) AC mains and its protective earth, regardless of whether the mains is live or non-live (standby). The unit is for land, marine, offshore, sub-sea and ocean floor use.
An AC or DC auxiliary voltage is required for the unit, if powered from a separate source the network can also be monitored during standby conditions. Only ONE KPM163x can be connected to each IT-system.
The ohmmeter and the triple-zone status LEDs give at a glance the clear safety message:
  • ALARM
  • WARNING
  • HEALTHY
General
IDV MEASURING PRINCIPLE
Insulation is measured between the complete galvanically interconnected AC network and its protective earth.
The unit injects a sequentially coded measuring signal into the monitored system. The signal flows to ground via the path of the insulation fault, the level of flow indicates the insulation resistance. The measuring accuracy is not influenced by any normal kind of load attached to the AC network.
Trip levels and delays are settable on unit rear. A trip LED flashes when the trip level is passed, the relay trips when the delay has elapsed. The timer resets if the fault is removed during countdown.
MEGGER SAFE
When auxiliary power is OFF the unit input is automatically protected against “megger” test voltages up to 1.4kVDC, and incorrect measurements caused by the unit’s input impedance are avoided.
OUTPUTS
All F versions have an isolated analogue output proportional to meter reading. If output is used for remote meter reading, we recommend 0-1mA for the slave indicator.
SAFETY
When a voltage adapter (CHx or ANx) is used the signal to terminals 4 and 6 on KPM163x is limited to a safe level, avoiding any dangerous voltage exposure to personnel.The KPM163x range is designed to comply with specification IMCA D 045 “Code of Practice for the Safe Use of Electricity Under Water” issued by IMCA. The unit meets EN 61010-1 Cat. III, Pollution degree 2 and the relevant environmental and EMC tests specified in EN 61326-2-4 to comply with the requirements of the major Classification Societies. NOTE Special versions of the KPM163x are available as:

KPM563x series
Insulation Guards with DC detection function, protected against high-energy DC voltage imposed on the monitored AC supply.
KPM263x series
Insulation Guards with measuring loop continuity monitoring.
INTELLIGENT SETTING ASSISTANCE
KPM163x has a built-in Assistance tool for setting/verification of the trip levels and the analogue output.
When either the Warning or Alarm potentiometer on the rear is operated by user, the meter goes into Assistance Mode and meter reading and analogue output will reflect the potentiometer setting.

Additional information

Weight 2 lbs
Dimensions 9 × 9 × 9 in
Model

KPM163E Insulation Monitor, Non-Latching Outputs, without Analog Output, KPM163G Insulation Monitor, Latching Outputs, without Analog Output, KPM163F Insulation Monitor, Non-Latching Output, with Analog Output, KPM163GF Insulation Monitor, Latching Outputs, with Analog Output, KPM163E2 Insulation Monitor, Non-Latching Outputs, without Analog Output, KPM163G2 Insulation Monitor, Latching Outputs, without Analog Output, KPM163F2 Insulation Monitor, Non-Latching Output, with Analog Output, KPM163GF2 Insulation Monitor, Latching Outputs, with Analog Output, KPM163H Insulation Monitor LDED, Non-Latching Outputs, without Analog Output, KPM163HG Insulation Monitor LDED, Latching Outputs, without Analog Output, KPM163HF Insulation Monitor LDED, Non-Latching Outputs, with Analog Output, KPM163HGF Insulation Monitor LDED, Latching Outputs, with Analog Output

Aux Supply

100-120VAC Aux Supply, 200-240VAC Aux Supply, 380-415VAC Aux Supply, 440-480VAC Aux Supply

Analog Output

Without Analog Output, 0-10mA Analog Output, 0-20mA Analog Output, 4-20mA Analog Output, 0-10VDC Analog Output