KPM169
Insulation Monitor for DC Systems 800-1200VDC, 10k-5MOhm Scale, Output Relay, optional Analog Output
-
Direct connection 12 to 48 VDC systems, up to 1600VDC with RH adapter
-
Precision reading unaffected of system voltage
-
All inputs and outputs fully isolated
-
Triple-zone insulation monitoring and Supervision relay
-
“Pathfinder” function eases faultfinding
-
Response time: 125-165mS
-
Indicates polarity of dominant earth fault
-
Analogue output proportional to meter reading (F/L-version)
Application
The digitally controlled KPM169 Insulation Monitor, DC Systems 800-1200VDC, 10k-5MOhm Scale, Output Relay, Analog Output monitors insulation level between a non-grounded (IT) battery or live DC network and its protective earth.
Only ONE KPM169x can be connected to the same DC-system. An AC or DC (standard) auxiliary voltage is required for the unit. A green LED indicates AUX POWER on. Start of monitoring function is delayed when auxiliary power is switched on (default 2 secs delay). In this way false tripping during power up, caused by initial charging of network spread capacitance, is avoided.
The DIN96 front-of-panel mounted instrument reads the insulation level directly in kΩ. The meter has reflection free glass. The ohmmeter and the triple-zone status LEDs at a glance gives the clear safety message:
-
ALARM
-
WARNING
-
HEALTHY
General
SEV MEASURING PRINCIPLE
Insulation is measured between the complete galvanically interconnected DC network and its protective earth. The signal flows to ground via the path of the insulation fault, the level of flow expresses the insulation resistance, the direction of flow expresses the fault polarity. The measuring accuracy is not influenced by any normal kind of load attached to the network. The detection time for an insulation fault is 125-165mS.
PATHFINDER/POLARITY FUNCTION
During a Warning or Alarm condition the Polarity LED indicates the polarity causing the trip:
-
POSITIVE EARTH FAULT: LED not lit
-
NEGATIVE EARTH FAULT: blue LED lit