KSQ332 Sector Check Synchronizing Relay with Dead Bus Facility

Call for price

Sector Check Synchronizing Relay with Dead Bus Facility
Download:
KSQ332x2 Brochure

Description

KSQ332x2

SECTOR CHECK SYNCHRONIZING RELAY WITH DEAD BUS FACILITY

  • Precision check synchroscope, sector principle
  • Dead-bus facility
  • Bi-directional synchronizing
  • Integral voltage differential protection, adjustable
  • “Easy view” status presentation
  • System status output
    Description
    KSQ332x2 provides both visual speed rotation, phase angel relationship and relay signal necessary to permit check synchronizing of two different system voltages.
    KSQ332E2 is the standard and it takes the auxiliary voltage from the monitored voltage on terminal 3 & 4.
    KSQ332G2 have separate auxiliary supply on terminal 19 & 20.
    The synchronizing relay will close when the incomer (generator, busbar, etc.) voltage and phase angle have been within the limits during the set retention time.
    A green lamp (CB close) indicates the close command to the breaker.
    There is lamp indication for reference source present (BUS PWR) and incomer status (GEN PWR).
    A green lamp (VOLT OK) is lit when the incomer voltage is within the set limits.
    When used as a dead-bus relay, the CB close relay will energize when the busbar supply is “dead”, generator voltage is connected and the enable contact is closed.
    Applications
    KSQ332x2 can be used both for single and three phase systems. Any two phases (or phase-neutral) can be used for synchronizing as long as it is the same two phases on both side of the breaker.
    The unit is meant for manual and semi-automatic synchronizing only since there is no compensation for the breaker closing time.
    For automatic synchronizing, the KCQ104x2 ”SPOT ON” principle should be used to obtain compensation for breaker closing delay.
    User setable limits and retention time on the rear.
    System status:
    KSQ332x2 is fitted with a system status relay. As standard the unit is powered from generator side (terminal 3 & 4), when power is ok and unit is working correctly the relay activates. It will release on alarm or when unit is not powered. Separate auxiliary supply is needed for continuously system status.
    Normal operation                : Closed contact
    Alarm condition/un-powered  : Open contact
    System “S” the sector synchronizing principle
    The KSQ332x2 is a low differential bi-directional check synchronizing relay.
    The synchronizing relay closes when the incomer (generator, busbar, etc.) frequency is close enough (diff 0,01 – 0,5Hz) to stay within the phase angle sector (S) for the set retention period (t).
    Sector synchronization is the classic alternative for applications which allow synchronization accuracy and duration of synchronization process to be interrelated. There is no compensation for the breaker closing time.
    Approximate synchronization accuracy relative to 12 o’clock position (Df) can be calculated by the following formula:
    Df = (S : 360) / t (secs)
    Example: Set phase angle (S) to 10 degrees and retention time (t) to 500mS to obtain an accuracy of Df:
    (10/360) / 0,5 =  0,055Hz
    If the phase angle limit is set too low and retention time too high for very low differential synchronizing, it can be difficult to achieve synchronization. If there is a continuously fluctuating load between the two systems (for example to synchronize against a shaft generator when a vessel is in rough weather), the KCQ104x2 “SPOT-ON” principle is more suitable.

Additional information

Weight 2 lbs
Dimensions 9 × 9 × 9 in
Model

KSQ332E2 Sector Check Synchronizing Relay w/o Aux Supply, KSQ332G2 Sector Check Synchronizing Relay w Aux Supply

Monitored Voltage

100-120VAC, 200-240VAC, 380-415VAC, 440-480VAC

Aux Supply

No Aux Supply, 100-120VAC Aux Supply, 200-240VAC Aux Supply, 380-415VAC Aux Supply, 440-480VAC Aux Supply, 12-24VDC Aux Supply