KPM163xQ Insulation Monitor, System Voltage up to 6.6kV with Non-Latching Output, Analog Output, Special for Frequency Converter Systems

Call for price

INSULATION MONITOR FOR NON-GROUNDED AC NETWORKS
Download:
KPM163FQ Brochure
Drawings:
KPM Dimensions

Description

KPM163xQ

Insulation Monitor, System Voltage up to 6.6kV, with Non-Latching Output and Analog Output, Special for Frequency Converter Systems

  • Designed for non-grounded networks with Frequency Converters
  • Direct connection up to 690V line voltage, up to 6.6kV with HV adapter 
  • Monitoring during both live and standby conditions
  • For use in land, marine and offshore Installations
  • “Megger” – safe to 1,4kVDC when aux power is OFF
  • Immune to earth capacitance and voltage surges
Application
The digitally controlled KPM163xQ is designed to monitor the insulation level between a non-grounded (IT) AC mains and its protective earth in systems with frequency converters . The unit is for land, marine and offshore use.
An AC or DC auxiliary voltage is required for the unit, if powered from a separate source the network can also be monitored during inactive (standby) conditions. Only ONE KPM163xQ can be connected to each IT-system.
The ohmmeter and the triple-zone status LEDs give at a glance the clear safety message:
  • ALARM
  • WARNING
  • HEALTHY
General
IDV MEASURING PRINCIPLE
Insulation is measured between the complete galvanically interconnected AC network and its protective earth.
The unit injects a DC measuring signal into the monitored system. The signal flows to ground via the path of the insulation fault, the level of flow indicates the insulation resistance. The measuring accuracy is not influenced by any normal kind of load attached to the AC network.
This unit is used for any land, marine or offshore installations. Start of monitoring function is delayed when auxiliary power is switched on (default 10 secs delay). The unit has minimum of 9 seconds detection time for any insulation fault.
Trip levels and delays are settable on unit rear. A trip LED flashes when the trip level is passed, the relay trips when the delay has elapsed. The timer resets if the fault is removed during countdown.
MEGGER SAFE
When auxiliary power is OFF the unit input is automatically protected against “megger” test voltages up to 1.4kVDC, and incorrect measurements caused by the unit’s input impedance are avoided.
OUTPUTS The KPM163xQ has an isolated analogue output proportional to meter reading. If output is used for remote meter reading, we recommend 0-1mA for the slave indicator.
SAFETY
The KPM163xQ range is designed to comply with specification AODC035 “Code of Practice for the Safe Use of Electricity Under Water” issued by IMCA.

High Voltage Adaptor for KPM163xQ

Voltage Adaptor is used for Insulation Guard KPM163xQ when the monitored line voltage is higher than 690VAC.
The adapter is a passive low-pass filter for use in 50, 60 or 400Hz networks, and is potted in polyurethane. The unit includes high inductance reactance modules, connected in a special configuration to avoid DC saturation.
Connection to the star-point (Neutral) is Preferable. The Adapter maintains a high AC suppression of its signal output to very low, safe levels, under all conditions. Alternative connections to the AC network.
INTELLIGENT SETTING ASSISTANCE
KPM163xQ has a built-in Assistance tool for setting/verification of the trip levels and the analogue output.
When either the Warning or Alarm potentiometer on the rear is operated by user, the meter goes into Assistance Mode and meter reading and analogue output will reflect the potentiometer setting.

Additional information

Weight 2 lbs
Dimensions 9 × 9 × 9 in
Model

KPM163EQ Insulation guard, direct up to 690V, up to 6.6kV with adapter, 0-10Mohm, KPM163EQG Insulation guard, direct up to 690V, up to 6.6kV with adapter, 0-10Mohm, Latching Output, KPM163FQ Insulation guard, direct up to 690V, up to 6.6kV with adapter, 0-10Mohm, Analog Output, KPM163FQG Insulation guard, direct up to 690V, up to 6.6kV with adapter, 0-10Mohm, Analog Output, Latching Output

Aux Supply

100-120VAC Aux Supply, 200-240VAC Aux Supply, 380-415VAC Aux Supply, 440-480VAC Aux Supply, 12-24VDC Aux Supply

Analog Output

No Analog Output, Analog Output 0-10mA, Analog Output 0-20mA, Analog Output 4-20mA, Analog Output 0-10VDC